MFG #SG3A0112KB0C
UPC #80342312396
SKU #4266313
Product description
HAMPS SG3A0112KB0C D16/NRC19 3PH 112.5KVA 480D-208Y/120VCU
HPS, SG3A0112KB0C, Distribution Transformer, Energy Efficient General Purpose, Series: Sentinel® G, 480 Delta VAC Primary, 208Y/120 VAC Secondary, 112.5 kVA Power, 60 Hz Frequency, 3 ph, Lug/Pad Connection, Floor Mounting, NEMA 3R Enclosure, 30 deg C, 98.74 % Efficiency, 36 in H x 28.3 in W x 27 in D Dimensions
HPS, SG3A0112KB0C, Distribution Transformer, Energy Efficient General Purpose, Series: Sentinel® G, 480 Delta VAC Primary, 208Y/120 VAC Secondary, 112.5 kVA Power, 60 Hz Frequency, 3 ph, Lug/Pad Connection, Floor Mounting, NEMA 3R Enclosure, 30 deg C, 98.74 % Efficiency, 36 in H x 28.3 in W x 27 in D Dimensions
- MSDS
Specification Sheet
- TRANSFORMER DISTRIBUTION 480 DELTAVAC
- RoHS Compliant|UL File No.E112313|CSA File No. LR3902
- Supplying Appliance, Lighting, Heating, Motorized Machine and Power Loads from Electrical Distribution System Applications
- HPS Sentinel® G Distribution Transformer, Energy Efficient General Purpose, 480 Delta VAC Primary, 208Y/120 VAC Secondary, 112.5 kVA Power, 60 Hz Frequency, 3 ph, Lug/Pad Connection, Floor Mounting, NEMA 3R Enclosure, 30 deg C, 98.74 % Efficiency, 36 in H x 28.3 in W x 27 in D Dimensions
- Meets latest U.S. DOE 10 CFR part 431 efficiency standards
Manufactured from quality non-aging, cold rolled, silicon steel laminations using state-of-the-art equipment
Cores are precision cut to close tolerances which eliminates burrs and improves performance
Core is coated to prevent the ingress of moisture
Precision wound with copper or aluminum conductors that are electrically balanced to minimize axial forces during short-circuit conditions
Robust interface between core & coils for better short circuit performance
Standard 150 deg C temperature rise and 220 deg C insulation class
ANSI 61 gray, UL50 enclosure finish
Front accessible separate high and low voltage terminals, connectors suitable for aluminum and copper are provided for easy cable installation
Side knockouts standard on all units bottom entry provision conduit entry
Typically 3.5% to 6.5% impedance
Generation 3 current design
Delta primary, wye-N secondary phase
40 deg C maximum temperature
ST-20 standards sound level
SCD 19 standard primary taps
DH3 case style
- Brand: Hammond Power SolutionsApplication: General purpose for supplying appliance, lighting, motorized machine and power loads from electrical distribution systems.Cooling: Convection cooledCountry of Origin: MULEnclosure: DH3-N3R - Indoor or OutdoorFrequency Rating: 60 HzHeight: 36 inInsulation Class: 220°CKVA Rating: 112.5Length: 27 inMounting: Floor (Opt. Wall/Ceiling Mount)Number Of Phases: 3Number Of Taps: ST-20 compliantPrimary Voltage: 480Secondary Voltage: 208Y/120 VSpecial Features: Meets current DOE 10 CFR part 431 (2016) and C802.2 efficiencies in an outdoor type enclosure. Smaller kVA sizes have standard input and/or output lugs, knockouts, and wall mounting brackets to save installation costs.Standard: RoHS Compliant|UL File No.E112313|CSA File No. LR3902Sub Brand: General Purpose TransformerTemperature Rating: Typical 30 Average/ 40 Maximum Deg CType: Transformer > Distribution > DOE 2016 Energy Efficient > General Purpose > Three PhaseWidth: 28.3 inWinding: Copper